Friday, December 14, 2012

HVAC Absorption Chillers vs Electric Chillers

In any HVAC system,selection of chillers involve many factors to be considered judiciously.These factors simultaneously present many advantages and disadvantages to end users.For the selection of water chillers,HVAC engineers consider all these factors keeping in view all the resources they have at their facility.
HVAC chillers
Absorption chiller vs electric chiller

Comparison of Absorption Chillers and Electric (Compression) Chillers

Following is the comparison of absorption chiller and electric chiller is presented below with aim to help you to decide the type of chillers for HVAC  system.
    absorption vs compression
  1. Absorption chillers have COP (coefficient of performance )of only 0.54–1.1 and it competes poorly with electric chillers (rotary compressor chillers). Electric chillers on other hand have COP from 1.0 ~ 8.0. 
  2. Absorption HVAC chillers occupy approximately 50% more floor area than the equivalent  electric chillers (vapor compression chillers). 
  3. Additionally due to height of absorption chillers, mechanical equipment rooms must be 6–10 ft taller than rooms housing electric chillers. Finally, because the liquid solution is  contained in long, shallow trays within an absorption chiller, the floor must be as close to absolutely level as possible.
  4. In HVAC system,Absorption chiller will weight at least twice as much the equivalent electric chiller  (vapor compression chiller). 
  5. Due to greater  size, absorption chillers are sometimes shipped in several sections, requiring field welding for final assembly.This is not case with counterpart electric chillers or compression chillers. 
  6. Most of electric water chillers are shipped from the factory with their refrigerant charge  installed.While the refrigerant and absorbent (including additives) must be field installed in absorption HVAC chillers. 
  7. When we talk about noise and vibration, absorption chillers (unless direct-fired) are quiet and essentially vibration-free as compared to compression chillers (electric drive chillers). Noise and vibrations in HVAC system annoy more than anything else . 
  8. Due to the potential for crystallization of the lithium bromide in the chiller if it becomes too cool, the condenser water temperature must be kept above 75–808F.There is no problem of crystallization in electric chillers (vapor compression chillers). Forget about the crystallization and stay cooled if you have installed compression chillers . 
  9. Absorption water chillers require sometimes an emergency power source if lengthy power outages are more often expected. Without power and heat input, the chiller begins to cool and the lithium bromide solution may crystallize. However, as absorption chillers consume very little electric energy so a small dedicated back-up generator can serve this purpose well. 
  10. HVAC system also gives importance to the amount of heat to be rejected in condenser by water cooling or air-cooling media.The heat rejection rate from the condenser of lithium bromide chiller is 20–50% greater than for the equivalent electric chiller, requiring higher condenser water flow rates and larger cooling towers and condenser water pumps. 
  11. Finally, an indirect-fired absorption water chiller will be at least 50% more expensive to purchase than the equivalent electric-drive chiller. Direct-fired absorption chillers will cost almost twice as much as an electric machine, and have the added costs associated with providing combustion air and venting (stack). 
  12. Absorption water chiller or lithium bromide chiller uses natural refrigerants such water and eliminate the need of CFC or HCFC refrigerants which have high global warming potential. 
  13. If you have plenty of waste heat or direct fire available ,and want to reduce your electric load ,then probably absorption chillers are the best solution.But obviously all above factors are to be considered for the selection of HVAC water chillers.

Friday, June 22, 2012

Absorption Chiller in HVAC system

Absorption chiller  occupies vital position in an HVAC system.Absorption chiller is an equipment which uses a heat source, a refrigerant and an absorbent for producing chilled or hot water. In the types of chillers,along with vapor compression water chiller or electric chiller ,absorption cooling system is also used in many applications.Absorption chillers produce chilled water under vacuum conditions for the purpose of air-conditioning and technology process.

Basic components of Vapor absorption chillers

Absorption chillers in its simplest form (single stage) consist of following main parts:


HVAC
Steam absorption chiller
  • Generator
  • Condenser
  • Evaporator
  • Absorber
  • Heat exchanger
  • Refrigerant Pump
  • Solution pump



Working Principle of Absorption Chiller

1. Function of Generator in absorption chiller

In generator of absorption chillers weak solution is heated by operating steam (steam absorption chillers),hot water or flue gases in indirect fired absorption chillers.While direct fired absorption chillers are Natural gas, Diesel or Kerosene Oil Operated.After heating in generator solution is concentrated and high temperature refrigerant vapors are produced.After generator process in a chiller high temperature and pressure refrigerant vapors travel to condenser. A strong solution enters absorber through heat exchanger in exchanging heat with weak solution .

2. Function of Condenser  in absorption chiller

water chiller
vapor absorption cycle
Refrigerant vapor from generator is condensed in condenser by cooling water.Condensation is constant pressure process where refrigerant (water) gives off its heat to cooling water .In this way refrigerant heat is carried to atmosphere.In water cooled chillers , cooling water recycles after exchanging heat with air in cooling towers of same HVACsystem.

3. Function of Evaporator in absorption chiller

Refrigerant from condenser flows to evaporator .In this compartment of absorption chiller,refrigerant gets vaporized by taking heat from chilled water.Refrigerant from evaporator refrigerant pan is pumped over the evaporator tubes with the help of refrigerant pump.Flow of refrigerant over evaporator tubes evaporates the refrigerant thus producing refrigeration effect, and evaporates to form vapor by absorbing heat of chilled water flowing through tubes.In this way,evaporation takes place at constant pressure process where refrigerant gets latent heat from chiller water.Chiller absorption takes place here in absorber.Chilled water is cooled and return to the system of customer.


4. Function of Absorber in absorption chiller

simplified diagram of  absorption chiller works
Produced refrigerant vapor enters absorber, and absorbed by strong solution in the absorber.In this way,strong solution is diluted by absorbing refrigerant vapor in absorber . Heat generated is carried to atmosphere by cooling water.

5. Function of HVAC Solution Pump in absorption chiller

This weak solution is transferred by solution pump to generator for concentration.Pumps are components in absorption cooling systems which require electric energy for its operation.Weak solution from the absorber is pumped into the generator through heat exchanger. This process is continued, and refrigeration effect is repeated.

Must Read : Absorption Chillers vs Electric (Compression) chillers